Armored Cable

*Product images are for illustrative purposes only and may differ from the actual product.

15kV - AIA - UL Type MV-105/MC - Shielded

Part #: Y34/003A

Aluminum Interlocked Armor
EPR Insulation - PVC Jacket
UL Type MV-105 or MC
15kV - 3-Conductor - Shielded

Construction
Category Conductor Description Bare copper Compact Class B strand
Conductor Shield Extruded semi-conducting thermosetting stress contol layer
Category Insulation Description Ethylene Polypropylene Rubber (EPR) 133% insulation level
Insulation Shield 8 mil copper tape with 25% overlap
Category Assembly Description The insulated and shielded power conductors shall be cabled round with fillers and with a grounding conductor in one outer interstice and covered with a binder tape
Armor A single strip of aluminum interlocked armor
Category Jacket Description Red Polyvinyl Chloride (PVC) Flame, sunlight & moisture resistant
  • Installed in wet or dry locations, indoors or outdoors, in exposed or concealed work
  • May be used in cable trays or on approved support in protected areas
  • Permitted for use in Class I; Class II, Divisions 1 and 2 hazardous locations per the NEC
  • UL Type MV-105
  • UL Type MC
  • UL 1581
  • UL 1072
  • IEEE 1202 available upon request
  • OSHA Acceptable

Questions & Answers