15kV - AIA - UL Type MV-105/MC - Shielded

*Product images are for illustrative purposes only and may differ from the actual product.

15kV - AIA - UL Type MV-105/MC - Shielded

Part #: Y31/003A

Aluminum Interlocked Armor
EPR Insulation - PVC Jacket
UL Type MV-105 or MC
15kV - 3-Conductor - Shielded

Construction
Category Conductor Description Bare copper Compact Class B strand
Conductor Shield Extruded semi-conducting thermosetting stress contol layer
Category Insulation Description Ethylene Polypropylene Rubber (EPR) 133% insulation level
Insulation Shield 6 mil copper tape with 25% overlap
Category Assembly Description The insulated and shielded power conductors shall be cabled round with fillers and with a grounding conductor in one outer interstice and covered with a binder tape
Armor A single strip of aluminum interlocked armor
Category Jacket Description Red Polyvinyl Chloride (PVC) Flame, sunlight & moisture resistant
  • Installed in wet or dry locations, indoors or outdoors, in exposed or concealed work
  • May be used in cable trays or on approved support in protected areas
  • Permitted for use in Class I Division 2, Class II Division 2, and Class III Divisions 1 and 2 hazardous locations per the NEC
  • UL Type MV-105
  • UL Type MC
  • UL 1581
  • UL 1072
  • IEEE 1202 available upon request
  • OSHA Acceptable

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Ground Gauge Jacket Thickness Nominal OD over Armor Nominal OD Overall Material Weight (Lbs./M')
Y30203A 2 3 6 0.06 2.08 2.21 2416
Y31/003A 1/0 3 4 0.075 2.22 2.35 2997
Y32/003A 2/0 3 4 0.075 2.31 2.44 3371
Y34/003A 4/0 3 3 0.075 2.53 2.7 4502
Y325003A 250 3 3 0.075 2.65 2.81 5005
Y335003A 350 3 2 0.085 2.85 3.01 6252
Y350003A 500 3 1 0.085 3.11 3.3 8091

Note: The data shown are approximate and subect to standard industry and manufacturer tolerances