Armored Cable

*Product images are for illustrative purposes only and may differ from the actual product.

5kV - AIA - UL Type MV-105 - Shielded

Part #: Y21/003A

Aluminum Interlocked Armor
EPR Insulation - PVC Jacket
UL Type MV-105 or MC
5kV/8kV - 3 Conductor - Shielded

x

Please select all above options before adding to cart.
Construction
Category Conductor Description Bare copper Compact Class B strand
Extruded Strand Shield Thermoset semi-conducting extruded stress control layer over conductor
Category Insulation Description Colored Ethylene Propylene Rubber (EPR) 5kV/133% insulation level 8kV/100% insulation level
Extruded Insulation Shield Thermoset semi-conducting polymeric layer free stripping from insulation
Grounding Conductor Annealed bare copper Class B stranding per ASTM B8
Shield Annealed copper tape with a minimum 25% overlap
Armor Aluminum interlocked armor
Category Jacket Description Flame and sunlight resistant yellow Polyvinyl Chloride (PVC)
  • Installed in wet or dry locations, indoors or outdoors, in exposed or concealed work
  • May be used in cable trays or on approved support in protected areas
  • Permitted for use in Class I; Class II, Divisions 1 and 2 hazardous locations per the NEC
  • UL Type MV-105
  • UL Type MC
  • UL 1072
  • IEEE-1202
  • OSHA Acceptable

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Ground No x AWG Nominal OD over Armor Outside Diameter Inches Material Weight (Lbs./M')
Y20203A 2 3 1 x #6 1.51 1.77 1819
Y21/003A 1/0 3 1 x #4 1.6 1.92 2364
Y22/003A 2/0 3 1 x #4 1.69 2 2696
Y24/003A 4/0 3 1 x #3 2.09 2.22 3687
Y225003A 250 3 1 x #3 2.21 2.34 4165
Y235003A 350 3 1 x #2 2.41 2.57 5436
Y250003A 500 3 1 x #1 2.64 2.84 7170

Note: The data shown are approximate and subect to standard industry and manufacturer tolerances