2.4kV - CCW Armored Power, Nonshielded, 3/C VFD

Part #: XMVE175003

UL Type MC-HL or MV-90, EPR
90°C
Cable Tray Use, Sunlight-Resistant, Direct Burial, ABS CWCMC

Construction
Category Conductor Description Bare annealed copper per ASTM B3 Compact stranding per ASTM B496
Extruded Strand Shield Extruded thermoset semi-conductor stress control layer over conductor per ICEA S-96-659 and UL 1072
Category Insulation Description 90 mils Ethylene Propylene Rubber (EPR) per ICEA S-96-659 and UL 1072 Insulation is printed 1-Black, 2-Red, and 3-Blue for phase identification
Grounding Conductor Three split Class B stranded bare annealed copper grounding conductors Sized in accordance with UL 1072 and NEC Table 250.122
Armor Continuous, impervious, welded, corrugated aluminum armor
Category Jacket Description Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC), yellow Low temperature performance meets ASTM D746 brittleness temperature at or below 40°C
  • Variable Frequency Drives: 3-conductor CCW armored cables with 3 symmetrical grounding wire are the preferred wiring method for use with AC motors controlled by pulse-width modulated inverters in VFD applications For use in feeders and branch circuits in industrial power distribution systems per NEC articles 328 and 330 Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, and 503 Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete