5kV EPR Insulation, PVC Jacket - Single Conductor, Compressed Stranding

Part #: MVE20201-SPX

EPR Insulation - PVC Jacket
MV-105, Compressed Stranded
Shielded - Single Conductor - 5kV

Construction
Category Conductor Description Annealed bare copper Compressed, Class B stranding
Extruded Strand Shield Extruded thermoset semi-conducting stress control layer over conductor
Category Insulation Description Ethylene Propylene Rubber (EPR), colored to contrast with the black conducting shield layers
Extruded Insulation Shield Thermoset semi-conducting polymeric layer free stripping from insulation
Metallic Shield 5 mils annealed copper tape with an overlap of 25%
Category Jacket Description Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)
  • Suitable for use in wet or dry locations in accordance with NEC
  • For use in aerial, direct burial, conduit, open tray, and underground duct installations
  • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5)
  • National Electric Code (NEC)
  • UL 1072
  • UL listed as Type MV-105 for use in accordance with NEC
  • ASTM B8
  • ICEA S-93 639
  • OSHA Acceptable

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Insulation Thickness Jacket Thickness Outside Diameter Inches Material Weight (Lbs./M')
MVE20201-SPX 2 .115 .060 .8060 498
MVE21/001-SPX 1/0 .115 .080 .9210 692
MVE22/001-SPX 2/0 .115 .080 .9640 801
MVE23/001-SPX 3/0 .115 .080 1.0150 937
MVE24/001-SPX 4/0 .115 .080 1.0710 1102
MVE225001-SPX 250 .115 .080 1.1170 1248
MVE235001-SPX 350 .115 .080 1.2200 1615
MVE250001-SPX 500 .115 .080 1.3480 2148
MVE275001-SPX 750 .115 .080 1.5270 2994

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances