2.4kV - Nonshielded - EPR/PVC Cable

*Product images are for illustrative purposes only and may differ from the actual product.

2.4kV - Nonshielded - EPR/PVC

EPR Insulation - PVC Jacket
2.4kV - MV-90 - Non-shielded

Construction
Category Conductor Description Compressed class B stranded tinned copper
Conductor Shield Nylon semi-conducting tape
Category Insulation Description 90°C rated Ethylene Propylene Rubber (EPR)
Category Jacket Description Extruded sunlight resistant Polyvinyl Chloride (PVC) jacket
  • UL listed
  • OSHA acceptable
  • Suitable for use in wet or dry locations at maximum operating temperature of 90°C for normal operation; 130°C for emergency overload conditions; and 250°C for short circuit conditions
  • May be installed in conduit, duct or aerially when properly supported by a messenger
  • ICEA S-96-659/NEMA WC 71
  • UL-1072
  • ASTM B3 and B8
  • RoHS Compliant

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Stranding Insulation Min Avg Wall(Mils) Nominal OD over Conductor Outside Diameter Inches Material Weight (Lbs./M')
MVE10401 4 7 0.125 .228 0.65 335
MVE10601 6 7 0.125 .181 0.605 231
MVE10201 2 7 0.125 .287 0.75 422
MVE11/001 1/0 19 0.125 .367 0.829 574
MVE12/001 2/0 19 0.125 .412 0.871 676
MVE14/001 4/0 19 0.125 .520 1.01 995
MVE125001 250 37 0.14 .566 1.127 1199
MVE135001 350 37 0.14 .670 1.229 1560
MVE150001 500 37 0.14 .800 1.357 2088
MVE175001 750 61 0.155 .983 1.55 2971

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances