Medium Voltage

*Product images are for illustrative purposes only and may differ from the actual product.

25 kV & 35kV - EPR Insulation, PVC Jacket

Part #: MVA42/001

Single Conductor - EPR Insulation - PVC Jacket
25kV/35 kV, EPR/Copper Tape Shield
Type MV-105
133% or 100% Insulation Levels

x

Please select all above options before adding to cart.
Construction
Category Conductor Description 1/0 AWG thru 1000 kcmil annealed bare copper compact Class B strand
Extruded Strand Shield Extruded thermoset semi-conducting stress-control layer over conductor
Category Insulation Description Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers
Extruded Insulation Shield Thermoset semi-conducting polymeric layer free stripping from insulation
Metallic Shield 5 mil annealed copper tape with an overlap of 25%
Category Jacket Description Low-friction, lead-free, flame-retardant, moisture and sunlight-resistant Polyvinyl Chloride (PVC)
  • Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial three-phase applications
  • For use in wet or dry locations when installed in accordance with NEC
  • For use in aerial, conduit, open tray and underground duct installations
  • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5)
  • National Electrical Code (NEC)
  • UL 1072
  • ICEA S-93-639/NEMA WC74
  • ICEA S-97-682
  • AEIC CS8
  • Type MV-105 for use in accordance with NEC
  • IEEE 1202 (70,000 BTU/hr)/CSA FT4
  • EPA 40 CFR, Part 261 for leachable lead content per TCLP method
  • OSHA Acceptable
  • RoHS Compliant

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductor Diameter Insulation Diameter Min Insulation Diameter Max Jacket Thickness Outside Diameter Inches Material Weight (Lbs./M')
MVA41/001 1/0 .340" 1.02" 1.12" 0.08 1.049 863
MVA42/001 2/0 .380" 1.06" 1.16" 0.08 1.35 925
MVA43/001 3/0 .430" 1.105" 1.205" 0.08 1.4 863
MVA44/001 4/0 .480" 1.16" 1.26" 0.08 1.45 1093
MVA425001 250 .530" 1.21" 1.315" 0.08 1.51 1174
MVA435001 350 .620" 1.31" 1.41" 0.08 1.6 1356
MVA450001 500 .740" 1.43" 1.53" 0.08 1.72 1707
MVA475001 750 .910" 1.61" 1.71" 0.11 1.96 2120
MVA4100001 1000 1.06" 1.76" 1.865" 0.11 2.1 2500

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances