Quadruplex Service Drop Cable
Part #: Mustang
600V Quadruplex
Aluminum Conductor
PE or XLPE Insulation
Part Number Table
Part # |
Houston Wire & Cable |
Phase Conductor AWG |
Phase Conductor Stranding |
Phase Conductor Insul. Thick. Mils |
Neutral AWG |
Bare Neutral Rated Strength Lbs. |
Lbs./M (XLP) |
Lbs./M (PE) |
Clydesdale |
- |
4 |
Solid |
45 |
4 |
881 |
199 |
198 |
Pinto |
- |
4 |
7 |
45 |
4 |
881 |
218 |
211 |
Mustang |
- |
2 |
7 |
45 |
2 |
1350 |
318 |
312 |
Criollo |
- |
1/ 0 |
19 |
60 |
1/ 0 |
1990 |
520 |
505 |
Percheron |
- |
2/ 0 |
19 |
60 |
2/ 0 |
2510 |
639 |
622 |
Hanoverian |
- |
3/ 0 |
19 |
60 |
3/ 0 |
3310 |
761 |
750 |
Oldenburg |
- |
4/ 0 |
19 |
60 |
4/ 0 |
4020 |
941 |
928 |
Lippizaner |
- |
336.4 |
19 |
80 |
336.4 |
6146 |
1519 |
1519 |
Morochuca |
- |
6 |
Solid |
45 |
6 |
1190 |
147 |
145 |
Chola |
HWC_Aluminum2013.pdf |
6 |
7 |
45 |
6 |
1190 |
158 |
153 |
Morgan |
- |
4 |
Solid |
45 |
4 |
1860 |
219 |
217 |
Hackney |
HWC_Aluminum2013.pdf |
4 |
7 |
45 |
4 |
1860 |
236 |
229 |
Palomino |
HWC_Aluminum2013.pdf |
2 |
7 |
45 |
2 |
2850 |
355 |
346 |
Costena |
HWC_Aluminum2013.pdf |
1/ 0 |
19 |
60 |
1/ 0 |
4380 |
566 |
551 |
Geiding |
- |
336.4 |
19 |
80 |
4/0 |
8350 |
1548 |
1494.3 |
Grullo |
HWC_Aluminum2013.pdf |
2/ 0 |
19 |
60 |
2/ 0 |
5310 |
697 |
680 |
Suffolk |
- |
3/ 0 |
19 |
60 |
3/ 0 |
6620 |
835 |
824 |
Appaloosa |
HWC_Aluminum2013.pdf |
4/ 0 |
19 |
60 |
4/ 0 |
8350 |
1063 |
1042 |
Gelding |
- |
336.4 |
19 |
80 |
4/ 0 |
8350 |
1548 |
1494 |
Bronco |
HWC_Aluminum2013.pdf |
336.4 |
19 |
80 |
336.4 |
8580 |
1613 |
1568 |
Bay |
- |
6 |
Solid |
45 |
6 |
1110 |
137 |
137 |
French Coach |
- |
6 |
7 |
45 |
6 |
110 |
146 |
146 |
German Coach |
- |
4 |
Solid |
45 |
4 |
1760 |
205 |
205 |
Arabian |
- |
4 |
7 |
45 |
4 |
1760 |
217 |
217 |
Belgian |
- |
2 |
7 |
45 |
2 |
2800 |
328 |
328 |
Shetland |
- |
1/ 0 |
19 |
60 |
1/ 0 |
4460 |
519 |
519 |
Thoroughbred |
- |
2/ 0 |
19 |
60 |
2/ 0 |
5390 |
639 |
639 |
Trotter |
- |
3/ 0 |
19 |
60 |
3/ 0 |
6790 |
789 |
789 |
Walking |
- |
4/ 0 |
19 |
60 |
4/ 0 |
8560 |
977 |
977 |
Hurricane |
- |
500 |
37 |
80 |
336.4 |
8520 |
2198 |
2180 |
*Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201
*Conductor temperature of 90°C for XLP, 75°C for Poly-ambient temperatures of 40°C
Note: The data shown is approximate and subject to standard industry and manufacturer tolerances