Instrumentation

*Product images are for illustrative purposes only and may differ from the actual product.

VNTC - Multiple Pairs - Overall Shield - 16 AWG & 18 AWG

VNTC® - Multiple Pairs
Overall Shield - 90°C
600 Volt - UL Type TC

Construction
Category Conductor Description Annealed Bare Copper 7 Strands Class B
Category Insulation Description Polyvinyl Chloride (PVC) & Nylon Black & White numbered pairs
Shield Aluminum Mylar Tape 100% coverage
Drain Wire 7 Strand Tinned Copper
Category Jacket Description Black, Polyvinyl Chloride (PVC)
  • Refer to NEC (NFPA 70) article 1277 for installation guidelines
  • Cable is suitable for use in Class I Division II hazardous locations
  • UL approved for direct burial, sunlight and oil I resistant applications
  • Cold Bend Rating -40°
  • UL listed as Type TC-ER per UL Standard 1277 for tray cables
  • Cable meets UL 1581 & 1202 (FT-4) 70,000 BTU/HR & ICEA T-29-520 210,000 BTU/HR requirements
  • Meets ICEA S-73-532, where applicable
  • All materials used in the manufacture

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Pairs Insulation Thickness Jacket Thickness Outside Diameter Inches Material Weight (Lbs./M')
L21802 18 2 .015 .045 .3460 70
L21804 18 4 .015 .045 .4500 109
L21806 18 6 .015 .060 .5570 164
L21808 18 8 .015 .060 .6280 211
L21812 18 12 .015 .060 .7310 282
L21816 18 16 .015 .060 .7860 361
L21824 18 24 .015 .080 .9710 565
L21836 18 36 .015 .080 1.3310 784
L21602 16 2 .015 .045 .4170 91
L21603 16 3 .015 .045 .4430 119
L21604 16 4 .015 .045 .4870 147
L21605 16 5 .015 .060 .5670 192
L21606 16 6 .015 .060 .6430 228
L21608 16 8 .015 .060 .6660 282
L21612 16 12 .015 .060 .7780 397
L21616 16 16 .015 .080 .9340 524
L21624 16 24 .015 .080 1.0950 749