FREP® - XHHW-2 FR-EP/CPE Jacket - 12 AWG - E-1 Color Code

CPE Jacket
EPR Insulation - XHHW-2 (VW-1)
90°C - 600 Volt - UL Type TC-ER*
E-1 Color Code

Construction
Category Conductor Description Fully annealed, stranded tinned copper per ASTM B33 Class B stranding per ASTM B8
Category Insulation Description Flame-retardant Ethylene Propylene Rubber (EPR)
Category Jacket Description Lead-free, flame-retardant thermoplastic Chlorinated Polyethylene (CPE)
  • Used as power and control cables in dry and wet locations Can be installed in cable trays, raceways, and open air Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
  • IEEE 1202 UL 44 (Type XHHW) UL 1581 VW-1 * UL Type TC-ER for 3 conductors or more

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Insulation Thickness Jacket Thickness Outside Diameter Inches Material Weight (Lbs./M')
AF161202 12 2 .030 .045 .2500 x .4100 82
AF161203 12 3 .030 .045 .4350 124
AF161204 12 4 .030 .045 .4750 157
AF161205 12 5 .030 .045 .5200 191
AF161207 12 7 .030 .060 .5950 268
AF161212 12 12 .030 .060 .7650 428

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances. *ER Rating only applies to 3 conductors or more; AF161202 has a flat construction.