Armored Cable

*Product images are for illustrative purposes only and may differ from the actual product.

600V - UL Type MC - 4 Conductor

Aluminum Interlocked Armor
90°C - 600 Volt
UL Type MC
4-Conductor

x

Please select all above options before adding to cart.
Construction
Category Conductor Description Bare compressed copper Class B stranding per ASTM B3 and B8
Category Insulation Description Flame-retardant Cross-linked Polyethylene (XLPE)
Category Assembly Description Conductors are cabled with suitable fillers and bare copper ground conductor Cable core is covered with binder tape
Spec Ground Annealed bare copper Class B stranding per ASTM B6
Armor Aluminum interlocked armor
Category Jacket Description Flame and sunlight resistant black PVC jacket
  • In all raceways or direct burial In wet or dry locations
  • Permitted for use in Class I, Division II and Class II, Division II, and Class III, Division I and II per NEC Article 334
  • UL 1569, UL 44, UL 1581, UL Type MC-600 volts
  • NEC Type XHHW-2 conductors
  • IEEE 1202
  • OSHA Acceptable

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Ground Gauge Insulation Thickness Jacket Thickness Nominal OD over Armor Nominal OD Overall Material Weight (Lbs./M')
Y11204A 12 4 12 0.03 0.05 0.58 0.71 272
Y11004A 10 4 10 0.03 0.05 0.68 0.77 355
Y10804A 8 4 10 0.045 0.05 0.81 0.9 494
Y10604A 6 4 8 0.045 0.05 0.91 1.01 655
Y10404A 4 4 8 0.045 0.05 1.01 1.13 891
Y10204A 2 4 6 0.045 0.05 1.15 1.28 1283
Y10104A 1 4 6 0.055 0.05 1.37 1.41 1584
Y11/004A 1/0 4 6 0.055 0.05 1.47 1.5 1900
Y12/004A 2/0 4 6 0.055 0.06 1.57 1.61 2356
Y13/004A 3/0 4 4 0.055 0.06 1.69 1.78 2916
Y14/004A 4/0 4 4 0.055 0.06 1.83 1.9 3596
Y125004A 250 4 4 0.065 0.06 1.99 2.07 4184
Y135004A 350 4 3 0.065 0.075 2.25 2.32 5628
Y150004A 500 4 2 0.065 0.075 2.57 2.66 7832
Y175004A 750 4 1 0.08 0.085 3.09 3.26 11825

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances