Tray Cable

*Product images are for illustrative purposes only and may differ from the actual product.

VNTC - DuPont Construction - 14 AWG

PVC Jacket
PVC/Nylon Insulation
90°C - 600 Volt - UL Type TC-ER*
DuPont Construction**
Method 4 Color code

Construction
Category Conductor Description Bare, annealed copper per ASTM B3 Class B stranding per ASTM B8
Category Insulation Description Flame-retardant Polyvinyl Chloride (PVC) with nylon tape
Category Jacket Description Black, sunlight-resistant, flame-retardant Polyvinyl Chloride (PVC) with ripcord
  • In free air, raceways and direct burial In wet and dry locations Class 1, Division 2 industrial hazardous locations per NEC Permitted for Exposed Run (ER) use in accordance with NEC for 3 or more conductors
  • UL 83 NEC Type THHN/THWN conductors UL 1277 Type TC-ER

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Jacket Thickness Outside Diameter Inches Material Weight (Lbs./M')
A141402 14 2 .045 .3200 57
A141403 14 3 .045 .3700 79
A141404 14 4 .045 .3730 93
A141405 14 5 .045 .3950 120
A141407 14 7 .045 .4390 155
A141409 14 9 .045 .5100 189
A141412 14 12 .060 .5910 284
A141415 14 15 .060 .6360 322
A141419 14 19 .060 .6900 400
A141437 14 37 .080 .9530 606

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances. *ER Rating only applies to 3 conductors or more; A141402 has a flat construction.