CCW Instrumentation; Ind. & Overall Shield; PVC Jacket; 90°C

*Product images are for illustrative purposes only and may differ from the actual product.

CCW Instrumentation; Ind. & Overall Shield; PVC Jacket; 90°C

Continuously Corrugated Welded Cable – CCW®
PVC/Nylon - PVC Jackets
Pairs & Triads – Individual & Overall Shields
90°C – 600 Volt

Construction
Category Conductor Description Bare, annealed copper conforming to ASTM B3 and stranded in accordance with ASTM B8 (Class B)
Category Insulation Description Flame-retardant Polyvinyl Chloride (PVC) insulation and nylon covering, rated 90°C per UL Standard 83 Color Code: ICEA Method 1
Individual Shield Isolated and individually twisted pairs or triads with an aluminum/polyester tape shield providing 100% coverage Drain wire
Overall Shield Aluminum/polyester tape shield providing 100% coverage Drain wire
Inner Jacket Flame retardant Polyvinyl Chloride (PVC) per UL 1569, black Low temp performance meets ASTM D746 brttleness temp at or below -40°C Nylon ripcord
Armor Impervious, continuously corrugated and welded aluminum per UL 1569 & 2225 Meets grounding requirements of NEC Article 250
Overall Jacket Flame-retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC) per UL Standards 1569, black Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C
  • For use as instrumentation tray cable on circuits rated 150V or less and 5 amps or less in accordance with NEC article 727
  • Recognized for use in Class I, II, and III, Divisions 1 and 2; or Class 1, Zones 1 and 2 hazardous locations per NEC articles 501, 502, 503 and 505
  • Installed indoors and outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays, or for direct burial
  • Recognized for use on fixed or floating offshore petroleum facilities as recommended by American Petroleum Institute
  • UL Type MC-HL
  • UL 83, 1569, 2225, 1309 and 1581
  • IEEE 1202 available upon request

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Pairs Triads Nominal OD over Core Nominal OD over Armor Nominal OD Overall Material Weight (Lbs./M')
XL41812 18 12 - .780 1.00 1.105 560
XL41824 18 24 - 1.08 1.39 1.49 969
XL41602 16 2 - .450 .670 .780 246
XL41604 16 4 - .560 .800 .910 346
XL41608 16 8 - .700 .930 1.04 502
XL41612 16 12 - .850 1.11 1.22 670
XL41624 16 24 - 1.12 1.42 1.53 1336
XL41636 16 36 - 1.37 1.69 1.82 2184
XL51604 16 - 4 .610 .840 .950 428
XL51608 16 - 8 .820 1.06 1.17 694
XL51612 16 - 12 .980 1.24 1.35 958

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances General Cable CCW® is a registered trademark of General Cable