Multitriad - Individual and Overall Shield Cable

*Product images are for illustrative purposes only and may differ from the actual product.

Multiple Triads - Individual & Overall Shields

Multiple Triads - 600 Volt
Individual & Overall Shield
90°C - UL Type TC

Construction
Category Conductor Description Stranded bare copper per ASTM B3 Class B stranding per ASTM B8
Category Insulation Description Flame retardant Polyvinyl Chloride (PVC) with nylon
Individual Shield Aluminum/polyester tape
Drain Wire Stranded, tinned copper
Overall Shield Aluminum/polyester tape
Category Jacket Description Flame retardant and sunlight resistant Polyvinyl Chloride (PVC)
  • Refer to NEC (NFPA 70) article 1277 for installation guidelines
  • Cable is suitable for use in Class I Division II hazardous locations
  • UL approved for direct burial, sunlight and oil I resistant applications
  • UL 1277 Type TC-ER
  • UL 1581 & 1202 (FT-4)
  • ICEA T-29-520
  • ICEA S-73-532, where applicable

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Triads Insulation Thickness Jacket Thickness Outside Diameter Inches Material Weight (Lbs./M')
L51804 18 4 0.015 0.06 0.567 185
L51808 18 8 0.015 0.06 0.743 328
L51812 18 12 0.015 0.08 0.901 495
L51824 18 24 0.015 0.08 1.221 959
L51602 16 2 0.015 0.06 0.567 161
L51604 16 4 0.015 0.06 0.638 250
L51608 16 8 0.015 0.08 0.857 472
L51612 16 12 0.015 0.08 1.076 699
L51616 16 16 0.015 0.08 1.191 942
L51624 16 24 0.015 0.08 1.331 1299
L51636 16 36 0.015 110 1.754 1994

Note: The information in this specification sheet is approximate and subject to standard industry and manufacturer tolerances *Printed Numbered Pairs are available upon request