FREP - XHHW-2 FR-EP/CPE Jacket - 10 AWG - K-1 Color Code Cable

*Product images are for illustrative purposes only and may differ from the actual product.

FREP® - XHHW-2 FR-EP/CPE Jacket - 10 AWG - E-1 Color Code

CPE Jacket
EPR Insulation - XHHW-2 (VW-1)
90°C - 600 Volt - UL Type TC-ER*
E-1 Color Code

Construction
Category Conductor Description Fully annealed, stranded tinned copper per ASTM B33 Class B stranding per ASTM B8
Category Insulation Description Flame-retardant Ethylene Propylene Rubber (EPR)
Category Jacket Description Lead-free, flame-retardant thermoplastic Chlorinated Polyethylene (CPE)
  • Used as power and control cables in dry and wet locations
  • Can be installed in cable trays, raceways, and open air
  • Suitable for exposure to weather, direct burial, and for Class 1 Division 2 hazardous locations as per NEC
  • IEEE 1202
  • UL 44 (Type XHHW-2)
  • UL 1581 VW-1
  • UL 1277 Type TC-ER
  • Rated for UV/Sunlight Resistant applications

Questions & Answers

Ask a Question

Part Number Table

Part # Gauge Conductors Insulation Thickness Jacket Thickness Outside Diameter Inches Material Weight (Lbs./M')
AF161002 10 2 0.03 0.045 .2700 x .4550 113
AF161003 10 3 0.03 0.045 0.485 172
AF161004 10 4 0.03 0.06 0.56 234
AF161005 10 5 0.03 0.06 0.615 284
AF161007 10 7 0.03 0.06 0.67 381
AF161009 10 9 0.03 0.06 0.785 488
AF161012 10 12 0.03 0.08 0.95 651

Note: The data shown are approximate and subject to standard industry and manufacturer tolerances. *ER Rating only applies to 3 conductors or more; AF161002 has a flat construction.