INSTRUMENTATION CABLE
VNTC® - Multiple Pairs
Overall Shield - 90°C
600 Volt - UL Type TC
Download PDF

CONSTRUCTION
Conductor: - Class B stranding per ASTM B8
- 7 strand bare copper per ASTM B3
Insulation: - Flame retardant PVC with clear polymide (nylon)
Shield: - Aluminum/polyester tape
Drain Wire: - Stranded, tinned copper
Color Code: - Per ICEA method 1; Pairs - Black and White - One conductor in each pair or triad is printed alphanumerically for easy identification
Color Code Chart:
Type Color
Pairs Black, White & Numbered
Jacket: - PVC, flame, moisture, and sunlight resistant
Applications:
- In raceways or direct burial
- In wet and dry locations
- Permitted for use in Class I Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type TC cables
Approvals:
- UL Type TC - 600 Volt
- NEC Type TFN conductors
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 Flame Test (70,000 BTU/hr)
- UL Listed Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
Part # AWG Size No. of Pairs Nom. Insul. Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
L21402 14 2 .020” .050” .565” 120 TCF05067A
L21404 14 4 .020” .060” .600” 257 TCF05067A
L21406 14 6 .020” .060” .685” 295 TCF07578A
L21408 14 8 .020” .060” .773” 428 TCF07578A
L21412 14 12 .020” .080” .985” 655 TCF100100A
L21416 14 16 .020” .080” 1.10” 835 TCF100109A
L21420 14 20 .020” .080” 1.19” 1035 TCF150140A
L21424 14 24 .020” .080” 1.33” 1250 TCF150140A
L21436 14 36 .020” .080” 1.55” 1675 TCF150165A
L21450 14 50 .020” .110” 1.83” 2435 TCF200186A
 

 
Site Designed By Triton Web Studios