INSTRUMENTATION CABLE
VNTC® - Multiple Pairs
Individual & Overall Shield
90°C - 600 Volt - UL Type TC
Download PDF

CONSTRUCTION
Conductor: - 7 strand bare copper per ASTM B3
- Class B stranding per ASTM B8
Insulation: - Flame retardant PVC with polymide (nylon)
Individual Shield: - Aluminum/polyester tape
Drain Wire: - Stranded tinned copper
Overall Shield: - Aluminum/polyester tape
Color Code Chart:
Type Color
Pairs Black, White & Numbered
Jacket: - Flame retardant and sunlight resistant PVC
Applications:
- In raceways or direct burial in accordance with NEC
- In wet or dry locations
- Permitted for use in Class I Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type TC cable
Features:
- Rated at 90°C dry, 75°C wet
- Provides sunlight, cold bend, and cold impact resistance
- Provides excellent oil and chemical resistance and a long service life
Approvals:
- UL Type TC - 600 Volt
- NEC Type TFN conductors
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 Flame Test (70,000 BTU/hr)
- UL Listed Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
Part # AWG Size No. of Pairs Nom. Insul. Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
L41602 16 2 .020” .045” .433” 108 TCF05054A
L41603 16 3 .020” .045” .460” 141 TCF05054A
L41604 16 4 .020” .060” .532” 191 TCF05054A
L41606 16 6 .020” .060” .632” 266 TCF05067A
L41608 16 8 .020” .060” .684” 333 TCF07578A
L41612 16 12 .020” .080” .862” 508 TCF10088A
L41616 16 16 .020” .080” .951” 645 TCF100100A
L41620 16 20 .020” .080” 1.08” 780 TCF100109A
L41624 16 24 .020” .080” 1.14” 919 TCF150140A
L41636 16 36 .020” .080” 1.33” 1316 TCF150140A
L41650 16 50 .020” .080” 1.53” 1772 TCF150165A
 

 
Site Designed By Triton Web Studios