TRAY CABLE
FREP®* - XHHW - 2 - (VW-1) - 90°
FR-EP Insulation - CPE Jacket
600 Volt - UL Type TC - 4 Conductor w/Ground
ER Rated
Download PDF

CONSTRUCTION
Conductor: - Stranded soft drawn tinned copper, Class B
Insulation: - Flame-retardant ethylene-propylene-rubber meeting the requirements for EPR VW-1 per UL
Assembly: - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary
- A binder tape (when required) of synthetic material assembles the core in a tight circular configuration
Color Code Chart 108:
Cond. Num. Cond. Marking Cond. Num. Cond. Marking
1 "1" One 2 "2" Two
3 "3" Three 4 "4" Four
Jacket: - Black sunlight resistant thermoplastic Chlorinated Polyethylene (CPE)
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial and for Class 1 Division 2 hazardous locations as per NEC
Standards:
- UL Type TC 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA S-95-658/NEMA WC70
- ICEA T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr)/CSA FT4
- IEEE 383 (70,000 BTU/hr)
- UL Subject 1277 (70,000 BTU/hr)
Part # AWG Size No. of Cond. Grd. Size Nom. Insul. Thick. Nom. Jacket Thick. Nom. O.D. Lbs./M’ Recommended Fitting
AF30804 8 4 10 .045” .060” .719” 439 TCF05078A
AF30604 6 4 8 .045” .060” .811” 627 TCF07588A
AF30404 4 4 8 .045” .080” .965” 897 TCF100100A
AF30204 2 4 6 .045” .080” 1.11” 1368 TCF125128A
AF30104 1 4 6 .055” .080” 1.21” 1430 TCF125128A
AF31/004 1/0 4 6 .055” .080” 1.34” 1934 TCF125147A
AF32/004 2/0 4 6 .055” .080” 1.46” 2332 TCF125147A
AF33/004 3/0 4 4 .055” .080” 1.60” 2870 TCF150165A
AF34/004 4/0 4 4 .055” .110” 1.79” 3630 TCF200186A
AF325004 250 4 4 .065” .110” 1.96” 4210 TCF200219A
AF335004 350 4 3 .065” .110” 2.21” 4743 4-300TC
AF350004 500 4 2 .065” .110” 2.54” 7881 4-300TC
AF375004 750 4 1 .080” .140” 3.11” 11746 4-350TC
 

 